Honeywell VPR100 User Manual page 290

Table of Contents

Advertisement

On-Site Adjustments
Error message
SLOT CARD FAILURE
STORAGE FAILURE
DATA STORAGE STATUS
LOST
RJ FAILURE
CLOCK FAILURE
CLOCK RESET
TIMING ERROR
TASK ERROR
RAM ERROR
COMM PORT ERROR
274
Table 9-9 Internal Error Messages (continued)
1. Check for noise. See Appendix B for noise suppression.
2. Check AI card connection.
3. Replace AI card.
1. Check for bad floppy disk.
2. Run disk diagnostic on the disk drive.
3. Check seating of floppy cables.
4. Replace CPU.
1. Check for bad floppy disk.
2. Run disk diagnostic on the disk drive.
3. Check seating of floppy cables.
4. Replace CPU.
1. Check reference junction sensor connection.
2. Check AI card.
3. Replace CPU.
1. Reprogram clock.
2. Reset unit.
3. Change lithium battery on CPU card.
4. Replace CPU.
1. Reprogram clock.
2. Reset unit.
3. Change lithium battery on CPU card.
4. Replace CPU.
1. Reprogram clock.
2. Reset unit.
3. Change lithium battery on CPU card.
4. Replace CPU.
1. Reset unit.
2. Clear configuration and reload.
3. If message recurs, replace CPU.
1. Run RAM diagnostic.
2. Replace CPU.
1. Check communications card seating.
2. Replace communications card.
3. Replace CPU.
VPR & VRX – User Manual
Suggested Action
12/00

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrx100Vrx150

Table of Contents