Table 4-54 Display Setup Procedure; Table 4-55 Set Up Trend 1 Prompts - Honeywell VPR100 User Manual

Table of Contents

Advertisement

Display Setup Procedure
Table 4-54 describes the display setup procedure.
Step
1
Select Program Displays from the Program mode menu.
2
For each display format desired (trend, bar graph, panel display, unit data), specify points to be
displayed.
3
Assign up to 10 displays to the Display button.
Set Up Trend 1
Table 4-55 describes the trend display setup procedure.
Prompt
ENABLE
YES, NO
POINT #1 POINT #6
Analog or discrete
(VPR100/VRX100)
parameters
POINT #1 - POINT #12
(VRX150)
NORMAL TIME
5, 15, 30 minutes, or 1, 2, 4,
BASE
8, 24 hours, 7, 31 days.
Equivalent paper chart
speeds are listed in Table
4-56.
ALT TIME BASE
5, 15, 30 minutes, or 1, 2, 4,
8, 24 hours, 7, 31 days.
Equivalent paper chart
speeds are listed in Table
4-56.
12/00

Table 4-54 Display Setup Procedure

Table 4-55 Set Up Trend 1 Prompts

Range/Selections
VPR & VRX – User Manual
Programming Function Blocks and Features
Action
Definition
Select YES to enable storage of this group of points. Enabled
trends are stored in a temporary buffer and can be scrolled
back in time.
Select NO to disable storage (and scrolling) of this group of
points.
Select up to 6 (12) analog or discrete points to be displayed
as a vertical or horizontal trend. Trends of discrete points will
show a value of 1 when ON and 0 when OFF.
Enter the trend display time base for Normal (typically slow
speed). The time base is the time period shown for one full
screen.
Enter the trend display time base for Alternate (typically fast
speed). The time base is the time period shown for one full
screen.