Programming Function Blocks and Features
Prompt
OFF or • 
MIN ON TIME
MIN OFF TIME
OFF or number
OUTPUT RELAY
Select discrete output
channel.
SENSITIVITY
NUMBER, OFF
DRIVE UNIT SPEED
NUMBER, OFF
SLIDEWIRE INPUT
OFF, NUMBER, PARM
102
Table 4-13 Analog Output Prompts (continued)
Range/Selections
VPR & VRX – User Manual
Definition
The minimum on time (in seconds) for the output. If the input
source calls for the output to be on for less than this time, the
output will not turn on at all.
Example 1
Impulse Time = 100. Min On Time = 5 seconds. The output
will not come on unless the input source is •   )RU
instance, if input source = 3%, output would be on for 3% of
impulse time, or 3 seconds, but since 3 seconds is less than
the Min On Time, output will not turn on.
Example 2
Impulse Time = 150. Min On Time = 3 seconds. The output
will not come on unless the input source is •   )RU
instance, if input source = 1%, output would be on for 1% of
impulse time, or 1.5 seconds, but since 1.5 seconds is less
than the Min On Time, output will not turn on.
The minimum off time (in seconds) for the output. If the input
source calls for the output to be off for less than this time, the
output will not turn off at all.
Example 1
Impulse Time = 100. Min Off Time = 5 seconds. The output
will not turn off unless the input source is ”   )RU
instance, if input source = 98%, output would be off for 2% of
impulse time, or 2 seconds, but since 2 seconds is less than
Min Off Time, output will not turn off.
Example 2
Impulse Time = 150. Min Off Time = 3 seconds. The output
will not turn off unless the input source is ”   )RU
instance, if input source = 99%, output would be off for 1% of
impulse time, or 1.5 seconds, but since 1.5 seconds is less
than the Min Off Time, output will not turn off.
This is the discrete output channel if using DAT output
algorithm. This discrete output will be unprogrammable
under the PROGRAM DISCRETE OUTPUTS programming
menu.
Enter the largest value that does not cause drive motor
oscillation.
The full scale travel time for the motor.
The AI block associated with the hardware input connected
to the slidewire (typically AI2).
The range of the feedback analog input must be
programmed for engineering units of 0 to 100 units, indirect
range, with a circuit span of 0 to 1 Vdc.
12/00