Table 5-16 Profiler Advance Procedure; Table 5-17 Profiler Shutdown Procedure - Honeywell VPR100 User Manual

Table of Contents

Advertisement

How to advance a profiler to the next segment
Step
1
Place profiler in Hold.
2
Press Down Arrow button to move cursor to
Advance. Press Enter.
3
To resume running the profiler, select Start.
How to shut down a profiler
Step
1
Place profiler in Hold by performing Profiler
holding procedure (Table 5-14).
2
Press Down Arrow button to move cursor to
Shutdown. Press Enter.
3
To resume running the profiler, select Start.
12/00

Table 5-16 Profiler Advance Procedure

Action

Table 5-17 Profiler Shutdown Procedure

Action
VPR & VRX – User Manual
Result/Notes
See Profiler Hold procedure in Table 5-14.
Profiler advances to next segment. Each press of
Enter advances the profiler one segment. If at the
last segment, the profiler advances to the first
segment. If it is a multiphase profile, the profiler
advances within the batch phase only. Events
assume their segment states.
Profile resumes running from the new segment.
Result/Notes
See Profiler Hold procedure in Table 5-14.
Profiler advances to the shutdown phase.
Profile resumes running from the beginning of the
shutdown phase.