en | Alarm
Address of logical zone
00005: the fifth logical zone triggered the first fire alarm.
Number of detectors
(6): In the fifth logical zone (00005), six detectors (6) triggered a fire alarm.
For logical zones that only consist of one element, no number of detectors is displayed.
Notice!
Depending on the configuration of the system, either the logical or physical address of the
detector is displayed.
Message number
The alarm messages are numbered chronologically.
The message number in the second line indicates the sequence in which the alarm messages
arrived.
#001: The first alarm message that came in.
Depending on the configuration, additional information is displayed in the second line, such as
the installation location of the logical zone.
8.4.5

The newest message

The latest message is always displayed at the end of the list.
The message number (e.g. #008) of the latest message indicates the total number of logical
zones in which one or more detectors have triggered an alarm.
8.4.6

Displaying the individual detectors in a logical zone

To display the individual detectors in a logical zone, select the logical zone you require.
The alarm messages for the individual detectors are listed.
8.4.7

Information about individual detectors

Each alarm message contains information about:
Example:
Fire
#002
Message type
Refer to Information about logical zones in the alarm state for information on the type of
message.
Message address
In this example, the following detector has triggered a fire alarm:
0005 - 004: the fourth detector (004) in the fifth logical zone (00005).
If the detector number, in this case (004), is not displayed, this is the alarm message for the
logical zone.
2020-07 | 3.0 | F.01U.378.877
The element category
The message type
The detector address
The message number
Depending on the configuration, additional information such as the installation location
Detectors
Office 1
00005 - 004
User Guide