Voice Alarm Systems - Bosch FPA‑5000 User Manual

Hide thumbs Also See for FPA‑5000:
Table of Contents

Advertisement

FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
Remote Alert
If you enable the Remote Alert service, an AVENAR panel 8000/2000 system pushes relevant
status information and events (e.g. alarms or fault messages) to the Bosch Remote Portal. In
case of an unexpected event, an alert can e.g. be delivered to a technician in form of SMS or
Email (if configured in the Remote Portal) so that relevant actions can be started at once.
Additionally to sending notifications, all events exported by the AVENAR panel 8000/2000
network are stored in the Bosch Remote Portal. This accumulated information can be
processed and analyzed to detect potential failures in the AVENAR panel 8000/2000 network
in advance.
In the Remote Services window you find information concerning the features and the status of
the Remote Services:
A list with information concerning the configured feature is displayed whereas RM is short for
Remote Maintenance, RA for Remote Alert. Please be aware that it's necessary to scroll down
in the list to see all information:
If a Remote ID is set in the panel, it automatically tries to connect to the RemotePortal. For a
manual connection attempt select Connect to server.
13.8

Voice alarm systems

Two different kinds of voice alarm systems can be connected to the AVENAR panel 8000/2000:
The diagnostic information displayed depends on the voice alarm system configured for the
AVENAR panel 8000/2000.
To display a list of all connected voice alarm systems that are used for voice evacuation:
1.
Bosch Sicherheitssysteme GmbH
In the start menu, select Diagnostics
Network services
Remote Services
System name: Name given to the system configuration in FSP-5000-RPS. If no name is
configured the serial number of the panel is used as system name.
Remote ID: Identification number for one specific service contractor. The Remote ID is
generated and provided by the RemotePortal. To newly enter or change the Remote ID
please see Remote Services.
System ID: identifies one AVENAR panel 8000/2000 system representing one FSP-5000-
RPS configuration. It is assigned to the panel by the RemotePortal server.
Status of Remote services: Shows if a remote connection to the RemotePortal server is
configured. (Enabled/Disabled).
Connection state: Only available at the panel which is configured as gateway panel.
Shows if the connection to the RemotePortal server is active (OK/Waiting for feedback/
Connection failed).
State of Condition Monitoring / State of Remote Alert: shows if the respective feature
was activated in the programming software FSP-5000-RPS.
RM/RA: State of last transfer: State of the last transfer of data from LSN devices
connected to the fire panel to the RemotePortal server (OK/Failed/Authentication failed)
RM/RA: Date of last transfer: Date and time of the last data transfer from an LSN device
connected to the fire panel to the RemotePortal.
For private secure network:
Server IP address: IP address of the server collecting and receiving data
Server port: Port number of the server collecting and receiving data.
Voice alarm system via serial interface module (Plena)
Voice alarm system (VAS) over IP (PRAESENSA, PAVIRO, Praesideo)
In the start menu, select Diagnostics