FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
Caution!
If the time to acknowledge or the time to investigate is exceeded, the alarm is immediately
!
forwarded to external stations.
To initiate alarm verification, select Acknowledge within the time shown to confirm the alarm.
Caution!
If the alarm is not confirmed within this time, it will be forwarded to external stations.
!
The time to investigate will be displayed. The alarm verification is initiated.
Test the fire alarm onsite within the specified time.
Caution!
If a second alarm is triggered during the alarm verification, all alarm messages are
automatically forwarded to external stations.
!
If, after conclusion of the alarm verification, a second alarm comes in — assuming alarm
verification is also possible for this alarm — then a time to investigate is initiated
automatically again.
9.7.3

Triggering alarm manually

Caution!
If, during the check, a real fire alarm is detected, then this alarm to the panel must be
!
manually forwarded to external stations such as the fire department. Alternatively, a manual
call point can be triggered at the location.
1.
2.
9.8

Resetting alarm message

Notice!
The detector can only be reset once the Reset time has elapsed. The reset time is configured
via FSP-5000-RPS.
When an element is reset, its initial status is restored. The activation of transmission devices
such as fire department or extinguishing devices is reset.
Depending on the configuration, three different variants are offered for resetting:
Bosch Sicherheitssysteme GmbH
To forward the alarm to external stations, select Manual alarm.
Select OK to confirm the operation.
The alarm is forwarded to the fire department:
In the LED display, the
Standard
Resetting all message types of the same message type:
All types of messages within the selected message type, such as Fire, are reset.
Resetting all elements that are not in the normal state
Displaying a submenu with four different selection options
Each displayed component can be reset individually:
This panel
To reset all elements that are not in the normal state
All elements in this event
icon turns red.
User Guide
Fire alarm | en
43
2020-07 | 3.0 | F.01U.378.877