6 Electrical Connection
The battery limited to a charging/discharging current of 10 A must be connected to the terminal
blocks C+ and C-.
BAT 20 A
_
+
Figure 17: Overview for connection of two batteries with varying charging/discharging current limits
6.8.1.3 Connection of one battery with a charging/discharging current
limit of 20 A
You may connect one battery with a charging/discharging current limit of 20 A each to the
inverter.
Procedure:
The DC terminals A and B must be switched parallely using the jumpers provided.
The battery must be connected to the terminal blocks A+ and A-.
BAT 20 A
_
+
Figure 18: Overview for connection of one battery with a charging/discharging current limit of 20 A
6.8.1.4 Connection of a battery with a charging/discharging current
limit of 30 A
You may connect one battery with a charging/discharging current limit of 30 A each to the
inverter.
Procedure:
All DC terminals must be switched parallely with the jumpers provided.
56
SBSxx-10-BE-en-11
BAT 10 A
_
+
A+ B+
A+ B+
C+
A− B−
C−
C+
A− B−
C−
SMA Solar Technology AG
DC-in
COM
AC-out
SPS
_
+
M1
M2
X1
X2
ANT.
FCC ID: SVF-KP20
IC: 9440A-KP20
A
B
D-IN
DC-in
COM
AC-out
SPS
_
+
M1
M2
X1
X2
ANT.
FCC ID: SVF-KP20
IC: 9440A-KP20
A
B
D-IN
Operating manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny boy storage 5.0Sunny boy storage 6.0

Table of Contents