SRX5600 Services Gateway Chassis Grounding Point Specifications

WARNING:
to ensure proper operation, you must properly ground the services gateway chassis
before connecting power. See
for instructions.
CAUTION:
attach cable lugs to the grounding and power cables that you supply. A cable with an
incorrectly attached lug can damage the services gateway.
The services gateway chassis has one grounding point at the upper right corner of the back panel. The
grounding point consists of two threaded holes spaced 0.625-in. (15.86-mm) apart
The grounding point holes fit UNC 1/4–20 screws. The accessory box shipped with the services gateway
includes the cable lug that attaches to the grounding cable and two UNC 1/4–20 screws used to secure
the grounding cable to the services gateway grounding point.
Figure 22: SRX5600 Services Gateway Grounding Point
To ground the services gateway, you must connect a grounding cable to earth ground and then attach it
to the chassis grounding point using the two screws provided.
To meet safety and electromagnetic interference (EMI) requirements and
"Grounding the SRX5600 Services Gateway" on page 220
Before services gateway installation begins, a licensed electrician must
(Figure 22 on page
61).