General Site Guidelines - Juniper SRX5600 Hardware Manual

Services gateway
Hide thumbs Also See for SRX5600:
Table of Contents

Advertisement

Table 31: Services Gateway Environmental Specifications
Description
Altitude
Relative humidity
Temperature
Seismic
Maximum thermal output
NOTE:
Install the services gateway only in restricted areas, such as dedicated equipment rooms
and equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National
Electrical Code, ANSI/NFPA 70.

General Site Guidelines

Efficient device operation requires proper site planning and maintenance and proper layout of the equipment,
rack or cabinet (if used), and wiring closet.
To plan and create an acceptable operating environment for your device and prevent environmentally
caused equipment failures:
Keep the area around the chassis free from dust and conductive material, such as metal flakes.
Follow prescribed airflow guidelines to ensure that the cooling system functions properly and that
exhaust from other equipment does not blow into the intake vents of the device.
Follow the prescribed electrostatic discharge (ESD) prevention procedures to prevent damaging the
equipment. Static discharge can cause components to fail completely or intermittently over time.
Install the device in a secure area, so that only authorized personnel can access the device.
Value
No performance degradation to 10,000 ft (3048 m)
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Normal operation ensured in temperature range of 32°F (0°C) to 104°F (40°C)
Nonoperating storage temperature in shipping container: –40°F (–40°C) to
158°F (70°C)
Designed to meet Telcordia Technologies Zone 4 earthquake requirements
AC power: 11,322.8 BTU/hour (3,318 W)
DC power: 9,632 BTU/hour (2,823 W)
161