Table 10- 40 PM240-2, IP20, FSD, 3 AC 380 V ... 480 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Table 10- 41 PM240-2, IP20, FSE, 3 AC 380 V ... 480 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power losses without filter
Power losses with filter
Required cooling air flow
Weight without filter
Weight with filter
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
6SL3210-...
...1PE27-5UL0
6SL3210-...
...1PE27-5AL0
37 kW
70 A
75 A
30 kW
62 A
60 A
3NE1 021-0 / 100 A
100 A
1.01 kW
1.02 kW
55 l/s
17 kg
18.5 kg
6SL3210-...
...1PE28-8UL0
6SL3210-...
...1PE28-8AL0
45 kW
86 A
90 A
37 kW
78 A
75 A
3NE1 022-0 / 125A
125 A
1.19 kW
1.2 kW
83 l/s
26kg
28 kg
10.2 Technical data, Power Modules
...1PE31-1UL0
...1PE31-1AL0
55 kW
104 A
110 A
45 kW
94 A
90 A
3NE1 224-0 / 160A
150 A
1.54 kW
1.55 kW
83 l/s
26 kg
28 kg
Technical data
401