Advertisement

Advanced commissioning
6.7 Application-specific functions
Example
In an open plan office, temperature sensors (Lg-Ni1000) are installed in three different
places. The inverter receives the measured values and temperature setpoint via its analog
inputs. A range from 8 °C ... 30 °C is permissible as setpoint temperature. The average
temperature should be 16 °C overnight.
Settings
p2200[0] = 1
p2251 = 0
p2900[0] = 16
p31020 = 1
p31021 = 0
p31022 = 7
p31023[0] = 755[0]
p0756[0] = 0
p0757[0] = 0 / p0758[0] = 8
p0759[0] = 10 / p0760[0] = 30 Upper value = 30 °C (10 V ≙ 30 °C)
p31023[1] = 2900
p31026[0]= 755.2
p0756[2] = 6
p0757[2] = 0 / p0758[2] = 0
p0759[2] = 100 / p0760[2] =
100
p31026[1] = 755[3]
p0756[3] = 6
p0757[3] = 0 / p0758[3] = 0
p0759[3] = 100 / p0760[3] =
100
p31026[2] = 755[1]
p0756[1] = 2
p0757[1] = 0 / p0758[1] = 0
p0759[1] = 20 / p0760[1] =
100
p31025 = 722.4
You will find more information about this multi-zone control in the parameter list and in
function diagram 7032 of the List Manual.
290
Technology controller enable
Technology closed-loop controller as main setpoint
Temperature setpoint overnight as a fixed percentage value
Activate multi-zone control
Multi-zone control with one setpoint and three actual values
Three actual values, one setpoint. The actual value of the
closed-loop control is the average value of three actual val-
ues.
Temperature setpoint via analog input AI 0
Select analog input type (voltage input 0 ... 10 V)
Lower value = 8 °C (0 V ≙ 8 °C)
p31023[1] interconnect with the value from p2900 for the re-
duction overnight
Temperature actual value 1 via analog input 2 as a percent-
age value
Analog input type (temperature sensor LG-Ni1000)
Lower value of the scaling characteristic
Upper value of the scaling characteristic
Temperature actual value 2 via analog input AI 3 as a &
Select analog input type (temperature sensor LG-Ni1000)
Lower value of the scaling characteristic
Upper value of the scaling characteristic
Temperature actual value 3 via a temperature sensor with
current output (0 mA ... 20 mA) via analog input AI 1
Analog input type (current input 0 ... 20 mA)
Lower value of the scaling characteristic (0 mA ≙ 0 °C)
Upper value of the scaling characteristic (20 mA ≙ 100%)
Switchover from day to night using digital input DI 4
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB