Table 10- 36 PM240-2, PT, frame sizes B, 3-ph. 380 V AC... 480 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Weight without filter
Weight with filter
1) approx. 0.16 kW through the heatsink;
Table 10- 37 PM240-2, IP20, frame sizes C, 3-ph. 380 V AC... 480 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Weight without filter
Weight with filter
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
6SL3211...
...1PE21-8UL0
6SL3211...
...1PE21-8AL0
7.5 kW
22.2 A
18.0 A
5.5 kW
19.8 A
13.7 A
3NE 1803-0 (35 A)
35 A Class J
0.2 kW
9.2 l/s
3.6 kg
3.9 kg
6SL3210...
...1PE22-7UL0
6SL3210...
...1PE22-7AL0
11.0 kW
32.6 A
26.0 A
7.5 kW
27.0 A
18.0 A
3NE 1817-0 (50 A)
50 A Class J
0.3 kW
18.5 l/s
4.7 kg
5.3 kg
10.2 Technical data, Power Modules
1)
...1PE23-3UL0
...1PE23-3AL0
15.0 kW
39.9 A
32.0 A
11.0 kW
36.0 A
26.0 A
3NE 1817-0 (50 A)
50 A Class J
0.37 kW
18.5 l/s
4.8 kg
5.4 kg
Technical data
399