Advanced commissioning
6.2 Inverter control
Defining the function of an analog input - example
Advanced settings
Signal smoothing
When required, you can smooth the signal, which you read-in via an analog input, using
parameter p0753.
For more information, see the parameter list and in the function block diagrams 9566 ff of the
List Manual.
Skip frequency band
Skip frequency band of the analog input
p0764[0]
p0764[1]
Using an analog input as digital input
An analog input can also be used as digital input. See also Section: Digital inputs
(Page 156).
162
To enter a supplementary setpoint via analog input AI 0, you
must interconnect AI 0 with the signal source for the supple-
mentary setpoint:
Set p1075 = 755[0].
Skip frequency band of the analog input AI 0 (factory setting: 0)
Skip frequency band of the analog input AI 1 (factory setting: 0)
Interferences in the cable can corrupt
small signals of a few millivolts. To be
able to enter a setpoint of exactly 0 V via
an analog input, you must specify a skip
frequency band.
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB