Advanced commissioning
6.7 Application-specific functions
Settings
Parameters
p2181
p2182
p2183
p2184
p2185
p2186
p2187
p2188
p2189
p2190
p2192
p2193 = 1
Monitoring, pump/fan
The monitoring functions for pumps and fans are similar. The blocking protection applies
equally to both applications.
For pumps, there is also a leakage monitoring function.
Principle of operation
Within speed thresholds 1 and 3, the inverter monitors the torque and the speed for pumps
and fans.
If the torque or the speed moves, for longer than the time set in p2192, in the ranges of
blockage, leakage or dry running protection/belt breakage, then the response defined in
p2181 is realized.
278
Description
Load monitoring response
Response when evaluating the load monitoring. Setting options see Response
options for the load monitoring (Page 280)
Load monitoring speed threshold 1
Load monitoring speed threshold 2
Load monitoring speed threshold 3
Load monitoring torque threshold 1, upper
Load monitoring torque threshold 1, lower
Load monitoring torque threshold 2, upper
Load monitoring torque threshold 2, lower
Load monitoring torque threshold 3, upper
Load monitoring torque threshold 3, lower
Load monitoring delay time
Delay time for the message "Leave torque monitoring tolerance band"
Load monitoring configuration (factory setting: 1)
see Table 6-39 Setting options for load monitoring (Page 276)
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Converter with CU230P-2 Control Units