4.5 Connecting the line supply, motor and converter components
4. Connect the temperature monitoring of the braking resistor (terminals T1 and T2 at the
braking resistor) to a free digital input in the inverter.
5. When commissioning the inverter, definine the function this digital input as external fault.
You have connected the braking resistor and ensured that temperature monitoring is set up.
Connecting a braking resistor to a PM330 Power Module
To connect a braking resistor to a PM330 Power Module, you require an external Braking
Module.
● Connect Braking Module at the DCP and DCN terminals of the Power Module.
● Connect the external braking resistor at terminals G and H of the Braking Module.
You can find additional information on the Internet: Hardware installation manual for PM330
Power Modules
(https://support.industry.siemens.com/cs/ww/en/view/90580072/64282054155).