Siemens SINAMICS G120 Operating Instructions Manual page 176

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.2 Inverter control
Bit
10
11
12
13
14
15
If you change over from another telegram to telegram 20, then the assignment of the previous
1)
telegram is kept.
176
Significance
Telegram 20
All other tele-
grams
0 = No control via PLC
1 = Control via PLC
1 = Direction reversal
Not used
---
1 = MOP up
1)
---
1 = MOP down Reduce the setpoint saved in the motorized
1)
CDS bit 0
Reserved
Explanation
Inverter ignores the process data from the
fieldbus.
Control via fieldbus, inverter accepts the pro-
cess data from the fieldbus.
Invert setpoint in the inverter.
Increase the setpoint saved in the motorized
potentiometer.
potentiometer.
Changes over between settings for different
operation interfaces (command data sets).
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Signal inter-
connection
in the in-
verter
p0854[0] =
r2090.10
p1113[0] =
r2090.11
p1035[0] =
r2090.13
p1036[0] =
r2090.14
p0810 =
r2090.15
Converter with CU230P-2 Control Units