Siemens SINAMICS G120 Operating Instructions Manual page 259

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

The inverter automatically acknowledges faults under the following conditions:
1)
p1210 = 1 or 26: Always.
p1210 = 4 or 6: If the command to switch-on the motor is available at a digital input or via the
fieldbus (ON/OFF1 = 1).
p1210 = 14 or 16: Never.
The inverter attempts to automatically switch the motor on under the following conditions:
2)
p1210 = 1: Never.
p1210 = 4, 6, 14, 16, or 26: If the command to switch-on the motor is available at a digital input
or via the fieldbus (ON/OFF1 = 1).
If, after a flying restart and magnetization (r0056.4 = 1) no fault occurs within one second, then the
3)
start attempt was successful.
Figure 6-39
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Time response of the automatic restart
Advanced commissioning
6.7 Application-specific functions
259