Compliance with standards
Standards
CE marking
Radio interference suppres-
sion
Approval
Ambient conditions
Ambient temperature
Relative humidity
(no condensation)
Corresponds to class
Environmental class / harm-
ful chemical substances
Organic/biological influences 1B1 according to EN 60721-
Pollution degree
Installation altitude
Mechanical strength
Vibrational load
- Displacement
- Acceleration
Shock load
- Displacement
- Acceleration
Deviations from the defined classes are shown in
maximum sound pressure level, ascertained in the IP20 cabinet
1)
Standard construction: Devices installed in the switch cabinet with EMC-conform construction, line reactor uk = 2%,
2)
shielded motor cable (e.g. Protoflex EMC) with max. 100 m cable length,
line perturbations according to EN 61000-2-4: Class 2, THD(U) total = 8 % for typical line conditions (RSC > 30 ... 50);
THD(I) total: typically 30 ... 45 % (15 < RSC < 50)
in transport packaging
3)
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
EN 60146-1-1, EN 61800-2, EN 61800-3, EN 61800-5-1, EN 60204-1, EN 60529, UL508C,
CSA 22.2 No. 14-13
To EMC directive No. 2004/108/EC and low-voltage directive No. 2006/95/EC
In accordance with the EMC product standard for variable-speed drives EN 61800-3, "sec-
ond environment"
. Application in "first environment" possible with line filters.
2)
cULus (File No.: E192450), CE, c-Tick, GOST-R, KC
During storage
3)
-25 ... +55 °C
5 to 95%
1K4 according to EN 60721-
3-1
1C2 according to EN 60721-
3-1
3-1
2 according to EN 61800-5-1
Up to 1000 m above sea level without derating,
> 1000 m above sea level with derating (see "Derating data")
During storage
3)
Fc test according to EN
60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g for 9 ... 200 Hz
italics
.
10.2 Technical data, Power Modules
During transport
3)
-25 ... +70 °C
°C
from –40
for 24 hours
5 ... 95 % at 40 °C
2K3 according to EN 60721-
3-2
2C2 according to EN 60721-
3-2
2B1 according to EN 60721-
3-2
During transport
3)
Fc test according to EN
60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g for 9 ... 200 Hz
Fc test according to EN
60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g for 9 ... 200 Hz
Technical data
During operation
0 ... +40 °C
up to + 50 °C with derating
5 ... 95 %
3K3 according to EN 60721-
3-3
3C2 according to EN 60721-
3-3
3B1 according to EN 60721-
3-3
During operation
Fc test according to EN
60068-2-6
0.075 mm for 10 ... 58 Hz
9.81 ma/s² (1 x g) for > 58 ...
200 Hz
Test according to EN 60068-
2-27 (EA shock type)
49 ma/s² (5 x g)/30 ms
147 ma/² (15 x g)/11 ms