Advertisement

Commissioning
5.3 Commissioning using a BOP-2 operator panel
10.
11.
12.
13.
14.
15.
16.
17.
18.
You have entered all of the data that is necessary for the basic commissioning of your
inverter.
124
Select the default setting for the interfaces of the inverter that is suita-
ble for your application. You will find the available default settings in
Section: Default setting of the interfaces (Page 88)
Minimum and maximum motor speed
Scaling of analog input 0
Motor ramp-up time
Motor ramp-down time
Ramp-down time for the OFF3 command
Motor data identification
Select the method which the inverter uses to measure the data of the
connected motor:
OFF
STIL ROT Recommended setting: Measure the motor data at stand-
STILL
ROT
Complete the basic commissioning:
18.1. Switch over the display using an arrow key: nO → YES
18.2. Press the OK key.
Motor data is not measured.
still and with the motor rotating.
Measure the motor data at standstill.
Select this setting if one of the following cases is applica-
ble:
• You have selected the control mode "SPD N EN".
However, the motor cannot rotate freely – for
example, if the traversing range is mechanically
limited.
• You have selected U/f control as control mode, e.g.
"VF LIN" or "VF QUAD".
Measuring the motor data while it is rotating.
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB