Siemens SINAMICS G120 Operating Instructions Manual page 321

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

PC/PG → inverter
Procedure
To transfer the settings, proceed as follows:
1. Go online with STARTER :
2. Select the button "Download project to target system":
3. To save the data in the inverter, select the "Copy RAM to ROM" button:
4. Go offline with STARTER :
You have transferred the settings.
Procedure with Startdrive
To transfer the settings from the PG to the inverter with Startdrive and activate the safety
functions, proceed as follows:
1. Save the project.
2. Select "Load to device."
Figure 7-1
3. Connect Startdrive online with the drive.
4. Click the "Start safety commissioning" button.
5. Enter the password for the safety functions.
If the password is the factory default, you are prompted to change the password.
If you try to set a password that is not permissible, the old password will not be changed.
6. Click the "End safety commissioning" button.
7. Confirm the prompt for saving your settings (copy RAM to ROM).
8. Disconnect the online connection.
9. Switch off the inverter supply voltage.
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
.
.
Activating settings in Startdrive
Backing up data and series commissioning
7.2 Saving settings on a PC
.
.
321