Lennox iComfort S30 Installation And Setup Manual page 64

Ultra smart thermostat
Hide thumbs Also See for iComfort S30:
Table of Contents

Advertisement

Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Applicable
Alert
Priority
System
Code
Condition
Component(s)
413
Critical
Outdoor unit
414
Moderate
Outdoor unit
415
Critical
Outdoor unit
Moderate /
416
Outdoor unit
Critical
Table 18. Alert Codes and Troubleshooting
Actual
Displayed Alert
Component or System Operational State and Troubleshooting Tip
Text
The high pressure switch has opened five times during one cooling demand.
Thermostat will shut down the outdoor unit.
Open high pressure switch error count reached five strikes.
Hi Pressure
Switch Strikes
Check system charge using superheat and sub-cooling temperatures.
Lockout
Check outdoor fan operation.
Check for dirt or debris blocking air flow to outdoor unit.
Reset by putting outdoor unit control in test mode or resetting low voltage power.
The discharge line temperature is higher than the recommended upper limit of 279ºF.
High
Discharge line temperature is greater than 279ºF.
Discharge Line
Make sure coil is clean and airflow unobstructed in and out of condenser.
Temperature
Check system operating pressures and compare to unit charging charts in installation manual.
The discharge line temperature has been consistently higher than the recommended upper limit
of 279ºF.
Hi Discharge
Discharge line high temperature error count reached five strikes during a single demand.
Line Temp
Make sure coil is clean and airflow unobstructed in and out of condenser.
Strikes Lockout
Check system charge using superheat and sub cooling temperatures.
Reset by putting outdoor control in test mode or resetting low voltage power.
The outdoor coil sensor is either open, short-circuited or the temperature is out of sensor
range.
Outdoor unit control will not perform demand or time / temperature defrost operation. (System
will still heat or cool.)
This fault is detected by allowing the unit to run for 90 seconds before checking sensor
Outdoor Coil
resistance. If the sensor resistance is not within range after 90 seconds, the control will display
Sensor Faulty
a moderate code.
Advances from moderate to critical after ten (10) minutes.
Plug-in sensor harness correctly. (Refer to Service and Application Note C-18-08)
Check resistance of sensor to determine if it is open, shorted, out of temperature calibration or
out of ambient temperature range. Replace if out-of-specifications.
64
How to clear alert code
Automatically clears when the
system detects that the issue no
longer exists.
Automatically clears after dis-
charge temperature is less than
225ºF.
Correct issue and cycle power to
the system.
Automatically clears when out-
door unit control detects proper
sensor readings.
If sensor is faulty and the system
is reporting the condition as
critical, replaced sensor. Reset
power to clear alert code.