Parameter
Description
This will notified the homeowner when the indoor temperature reaches the setting defined for this parameter.
Freezing Alert
Temperature
Range is 30°F to 50°F (-1.11 to 10.0°C) with a factory default of 40°F 4.4°C). Increments adjusted by 1.0°F (0.56°C).
Single Setpoint Mode (SSP)
(Non-Zoning System Only)
On the user screens this is referred to as Perfect Temp (Temperature). Options are enabled or disabled. Default is disabled. The Single Set Point (SSP) algorithm allows the user the set only one
temperature set point value rather than one value for heating and a different value for cooling. When zoning is present, the following SSP settings are not available. When enabled the following
parameters are automatically configured for optimal settings.
SSP Heating
Cancel Coast
Range is 0 to 0.75°F (0.0 to 0.42°C). Default is 0.25°F (14°C). Adjustments are in increments of 0.125°F (0.07°C).
Counter
Increment Slope
SSP Heating
Cancel Coast
Counter
Range is 0.25 to 2°F (0.14 to 1.11°C). Default is 0.5°F (0.28°C). Adjustments are in increments of 0.125°F (0.07°C).
Decrement
Slope
SSP Cooling
Cancel Coast
Range is -0.75 to 0.0°F (-0.42 to 0.0°C). Default is -0.25°F (-0.14°C). Adjustments are in increments of 0.125°F (0.07°C).
Counter
Increment Slope
SSP Cooling
Cancel Coast
Counter
Range is -2.0 to -0.25°F (-1.11 to -0.14°C). Default is -0.5°F (-0.28°C). Adjustments are in increments of 0.125°F (0.07°C).
Decrement
Slope
SSP Heating
When the outdoor temperature is above this setting, heating is not allowed if single set point is running.
Lockout Outdoor
Range is 50 to 80°F (10.0 to 26.67°C). Default is 70°F (21.11°C). Adjustments are in increments of 1.0°F (0.56°C).
Temp
SSP Cooling
When the outdoor temperature is below this setting, cooling is not allowed if single set point is running.
Lockout Outdoor
Range is 30 to 60°F (-1.11 to 15.56°C). Default is 40°F (4.44°C). Adjustments are in increments of 1.0°F.
Temp
Options are disabled, conservative, medium and aggressive. Default is disabled.
Disable - There is no monitoring of Smart Alert Enable.
Conservative - The system will wait longer to display any Smart Alert Enable alarms. This options allow for a minimum chance for false alarms being shown.
Medium (default) - Extensive testing by the Lennox development team to minimize the number of false alarms.
Aggressive - Will shorten time to display any Smart Alert Enable alarms.
Smart Alert Enable function monitors:
Smart Alert
Thermostat set point setting
Enable
Temperature reading
Determine whether the system moving towards the desired temperature setting or is unable to achieve the desire temperature setting.
Uses local climate design temperatures
System run times.
NOTE:
Smart Alert Enable feature is disabled in a zoning system.
NOTE:
Depending on type of system (conventional heating/cooling or heat pump system) and optional equipment not all system settings will be displayed.
Table 4. Smart Hub Parameters