Lennox iComfort S30 Installation And Setup Manual page 59

Ultra smart thermostat
Hide thumbs Also See for iComfort S30:
Table of Contents

Advertisement

Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Applicable
Alert
Priority
System
Code
Condition
Component(s)
273
Critical
Furnace
274
Critical
Furnace
275
Critical
Furnace
276
Critical
Furnace
290
Critical
Furnace
291
Critical
Furnace
Furnace or air
292
Critical
handler
294
Critical
Furnace
295
Minor
Furnace
Table 18. Alert Codes and Troubleshooting
Actual
Displayed Alert
Component or System Operational State and Troubleshooting Tip
Text
The furnace flame is going off during a heating cycle. The system will go into WatchGuard
mode.
WatchGuard
Check micro-amperes of flame sensor using thermostat diagnostics.
- Flame fail in
Clean or replace sensor.
Run Mode
Measure voltage of neutral to ground to ensure good unit ground.
Clean face of burner assembly.
The furnace limit switch has been open for more than three minutes. The system will go into
WatchGuard -
WatchGuard mode.
Primary Limit
Check firing rate and air flow.
Switch Open
Check for air blockage.
The furnace flame is out of sequence. The system will go into WatchGuard mode.
WatchGuard -
Flame Out of
Shut off gas.
Seq. No Flame
Check for gas valve leak.
The furnace is not able to calibrate or the high pressure switch opened or failed to close in run
WatchGuard
mode. The system will go into WatchGuard mode.
- Calibration
Check vent system
Failure
Check pressure switch wiring connections.
There is a problem with the furnace ignition circuit. The system will go into WatchGuard mode.
Measure resistance of hot surface igniter.
Ignition Circuit
Problem
Replace the hot surface igniter; it is not within specifications.
Measure voltage to igniter.
The heating airflow is below the minimum required level. The system will go into WatchGuard
Heat Airflow
mode.
Restricted
Check for dirty air filter(s) and other air flow restrictions.
Below Min
Check blower performance.
The indoor unit blower motor will not start. The system will go into WatchGuard mode.
Indoor blower motor unable to start.
Indoor Blower
Motor Start
This could be due to seized bearing, stuck wheel, and obstructions.
Problem
Replace motor, motor module or wheel if assembly does not operate or meet performance
standards.
There is over current in the furnace inducer motor. The system will go into WatchGuard mode.
Inducer Motor
Check combustion blower bearings, wiring and amps.
Overcurrent
Replace furnace inducer motor if it does not operate or does not meet performance standards.
The indoor blower motor is overheating. Indoor blower motor over temperature (motor tripped on
internal protector).
Indoor
Check motor bearings and amps.
Blower Over
Temperature
Replace indoor blower motor if necessary.
Check for high duct static.
59
How to clear alert code
Automatically clears when a heat
call ends successfully.
Automatically clears when a heat
call ends successfully.
Automatically clears on success-
ful ignition.
Automatically clears when the
furnace calibrates itself success-
fully.
Automatically clears on success-
ful ignition
Automatically clears when a heat
call ends successfully.
Automatically clears after the
indoor blower motor starts suc-
cessfully.
Automatically clears after inducer
motor current is sensed to be in-
range after the ignition following
either WatchGuard mode or unit
reset.
Automatically clears after blower
demand is satisfied.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents