Lennox iComfort S30 Installation And Setup Manual page 57

Ultra smart thermostat
Hide thumbs Also See for iComfort S30:
Table of Contents

Advertisement

Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Applicable
Alert
Priority
System
Code
Condition
Component(s)
223
Critical
Furnace
224
Critical
Furnace
225
Moderate
Furnace
226
Critical
Furnace
227
Moderate
Furnace
228
Moderate
Furnace
229
Minor
Furnace
240
Moderate
Furnace
Table 18. Alert Codes and Troubleshooting
Actual
Displayed Alert
Component or System Operational State and Troubleshooting Tip
Text
The furnace low pressure switch is open.
Check pressure (inches w. c.) of the low pressure switch closing during a heat call.
Low Pressure
Measure operating pressure (inches w. c.).
Switch Open
Inspect vent and combustion air inducer for correct operation and restriction.
Check for blocked cold end heater box or condensate drain and cracked hoses.
The furnace low pressure switch is stuck closed.
Check operation of low pressure switch to see if it is stuck closed for longer than 150 seconds
Low Pressure
during a heat call.
Switch Stuck
Closed
Measure operating pressure (inches w. c.).
Inspect vent and combustion air inducer for correct operation and restriction.
The furnace high pressure switch will not close.
Check pressure (inches w. c.) of high pressure switch closing during a heat call.
High Press.
Switch Failed to
Measure operating pressure (inches w. c.).
Close
Inspect vent and combustion air inducer for correct operation and restriction.
Check for blocked cold end heater box or condensate drain and cracked hoses.
The furnace high pressure switch will not open.
High Pressure
Check operation of high pressure switch closing during a heat call.
Switch Stuck
Measure operating pressure (inches w. c.).
Closed
Inspect vent and combustion air inducer for correct operation and restriction.
The furnace low pressure switch is open while in run mode.
Check pressure (inches w. c.) of low pressure switch closing during a heat call.
Lo Pressure
Switch Open in
Measure operating pressure (inches w.c.).
Run Mode
Inspect vent and combustion air inducer for correct operation and restriction.
Check for blocked cold end heater box or condensate drain and cracked hoses.
The furnace control is not able to calibrate the pressure switch. Unable to perform pressure
switch calibration.
Inducer / Press.
Check vent system and pressure switch wiring connections.
Switch Calib.
Failure
Check the drain trap for blockage.
Check for blocked cold end heater box or condensate drain and cracked hoses.
Ignition on High
Furnace control switched to high fire ignition because low fire pressure switch did not close in
Fire
allowed time.
The furnace flame current is low.
Check micro-amperes of the flame sensor using thermostat diagnostics.
Low Flame
Clean or replace the flame sensor.
Current - Run
Measure voltage of neutral to ground to ensure good unit ground.
Mode
Clean face of burner assembly.
Check for AC voltage from flame sensor electrode to ground.
57
How to clear alert code
Automatically clears after the
issue is corrected.
Automatically clears after the
issue is corrected.
Automatically clears after the
issue is corrected.
Automatically clears after the
issue is corrected.
Automatically clears after the
issue is corrected.
Automatically clears after a
successful calibration.
No action is required.
Automatically clears after a
proper micro-amp reading has
been sensed.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents