■Usage: Program control(PLC)
Item
(a)
Usage
(b)
Protocol
(c)
Unit No.
(d)
Baud rate
(e)
Data length
(f)
Parity
(g)
Stop bit
Description
Set usage for serial communication.
<Initial> Data collection(ELC)
<Set range> Data collection(ELC) / Program control(PLC)
*3
Set communication protocol.
<Initial> MEWTOCOL-COM master/slave
<Set range>
*4
Set unit number of ELC500.
<Initial> 1
<Set range>
MEWTOCOL-COM master/slave:
MEWTOCOL7-COM slave:
MODBUS RTU master/slave:
General communication:
Set baud rate.
<Initial> 19200bps
<Set range> 300/ 600 / 1200 / 2400 / 4800 / 9600 / 19200 /
*5
Set data length.
<Initial> 8bit
<Set range> 7bit / 8bit
Set parity.
<Initial> Odd
<Set range> None / Odd / Even
Set stop bit.
<Initial> 1bit
<Set range> 1bit / 2bit
MEWTOCOL-COM master/slave
MEWTOCOL7-COM slave
MODBUS RTU master/slave
General communication
PLC link
*2
38400 / 57600 / 115200 / 230400
63
ELC500 Control unit
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
(j)
(k)
*1
1 to 99
1 to 999
1 to 247
1 to 999