Panasonic ELC500 User Manual page 136

Table of Contents

Advertisement

Item
(a)
No.
(b)
Name
(c)
Start trigger
(d)
Alarm 3 control time [time A] Set time to start (control time).
(e)
Alarm 3 cancel time [time B] Set time to start next group. (cancel time).
(f)
Remote I/O output
(g)
Group
*1 It doesn't start 'Start control' without the trigger.
Point
- Start control is controlled by output pattern of remoter I/O unit for alarm 3 and no alarm.
In order to use start control, set remote I/O unit so that it power off at alarm 3 and it power
on at no alarm.
Note
- When the same trigger is selected, a trigger with smaller registered number has a priority.
- In case of setting remote I/O unit to remote I/O output, when it shifts RUN mode to
STOP/PROG mode, ELC500 writes output status with no alarm to the registered remote
I/O unit.
Description
Set from 1 to 4.
Set Name
<Set range> 32-letter or less
*1
Set trigger to start 'Start control'.
Except trigger of appointed period
<Set range> 1 to 60[min]
<Set range> 1 to 60[min]
Shift to Remote I/O unit setup window.
Register I/O device before this.
Register control group for I/O devioces.
Register control group for remote I/O units.
Set order to control when it start 'Start control'.
N/A
Group 1
Group 2
Group 3
Group 4
Remove the target of start control.
Output status = No alarm
Register remote I/O unit in group 1
Register remote I/O unit in group 2
Register remote I/O unit in group 3
Register remote I/O unit in group 4