■Setup for Fixed-time demand (Moving average power method)
Item
(a)
Name
(b)
Trigger
(c)
Period
(d)
Alarm mask time
(e)
Use the data of the previous
period for demand
estimation.
(f)
Control demand value
(g)
Limit control demand value
(h)
Target demand value
(i)
Switch moving average time Select use the function, that it switches period 1st half and
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
(j)
(k)
(l)
Description
Set name for demand control pattern
<Set range> 32-letter or less
Set trigger from the registered trigger.
It works alarm function at this trigger, it works alarm function.
Set demand period.
<Initial>30 min
<Set range>15 / 30 / 60
Set alarm mask time.
<Initial> 0 min
<Set range> 0 to 10
Select use the function, it calculates estimated demand
using the incline of power in the previous period, or not.
<Initial> without check = not available
Set control demand value
<Initial> 0 kW
<Set range> 0 to 999999999999999
Set limit control demand value
<Initial>0 kW
<Set range> 0 to 999999999999999 kW
Set target demand value
<Initial>0 kW
<Set range>0~999999999999999 kW
2nd half for calculate demand value increasing rate to
estimate dimmed, or not
<Initial> Yes
110
ELC500 Control unit