Hitachi SJ Series User Manual page 499

Hide thumbs Also See for SJ Series:
Table of Contents

Advertisement

Chapter 14
14.3.3
Function codes
• Specify functions the inverter executes using function
codes.
Function code
Function Code
Function
01h
Reads out the state of coil.
03h
Reads out the content of retention
register.
05h
Writes to coil.
06h
Writes to retention register.
08h
Loopback test
0Fh
Writes to multiple coils.
10h
Writes to multiple retention registers.
17h
Writes / reads out to multiple retention
registers.
14.3.4
Data
• Transmit the data related to function codes.
• The inverter corresponds to the data formats shown
below among data used in Modbus.
Data Name
Coil
Retention register
Corresponding function codes are shown below:
Max. Data Bytes Handled by
1 Message
4
32
2
2
-
4
32
32 / 32
• Transmission formats of data vary depending on function
codes.
Description
Writable/readable binary data (1 bit long)
Writable/readable 16 bits long data
14-8
RS485 Communication
Max. Number of Data
Handled by 1 Message
32 coils (bitwise)
16 registers (in bytes)
1 coil (bitwise)
1 register (in bytes)
-
32 coils (bitwise)
16 registers (in bytes)
16 / 16 registers (in bytes)