12.10.4
PID Sleep
PID sleep function
A
• In the case of using this function, set 01 (output
low) or 02 (SLEP terminal) to PID sleep condition
selection [AH-85].
• You can change the start/cancel time and level of
the sleep operation depending on the usage.
Parameter
Item
PID sleep condition selection
PID sleep start level
PID sleep operation time
Boost selection prior to PID
sleep
Boost time prior to PID sleep
Boost amount prior to PID
sleep
Minimum operation time prior
to PID sleep
PID sleep status minimum
retaining
time
PID wake condition selection
PID wake start level
PID wake operation time
PID wake start deviation
amount
Input terminal function
Item
PID sleep start terminal
PID sleep cancel terminal
Parameter
Data
00
01
[AH-85]
02
[AH-86]
0.00~590.00(Hz)
[AH-87]
0.00~100.00(s)
00
[AH-88]
01
[AH-89]
0.00~100.00(s)
[AH-90]
0.00~100.00(%)
[AH-91]
0.00~100.00(s)
[AH-92]
0.00~100.00(s)
01
[AH-93]
02
03
[AH-94]
0.00~100.00(%)
[AH-95]
0.00~100.00(s)
[AH-96]
0.00~100.00(%)
Terminal
Data
name
[SLEP]
057
[WAKE]
058
12-10-17
• You can choose cancellation of the PID sleep
status from 01 (deviation amount), 02 (feedback
low), and 03 (WAKE terminal) of the PID wake
condition selection [AH-93].
• In the case of canceling the PID sleep status by
deviation, cancellation will only be activated when
deviation increases in a direction of lower output,
even if PID1 deviation [AH-02] was set to 01 and
PID deviation ± was switched.
Disable
Starts sleep operation when output is low
Starts operation at the rising edge of
the [
SLEP] terminal
Is a level of making a judgment of sleep
operation for the output speed when
[AH-85] = 01.
Is stand-by time before shifting to sleep
operation.
Disable
Boosts target value before sleep operation.
Is actuation time prior to PID sleep.
Sets a boost amount to be added to target
value before sleep.
Does not start sleep operation until [AH-91]
has elapsed from start.
Retains the sleep status until [AH-92] has
elapsed, once the sleep operation started.
Cancels the sleep operation when a
deviation amount increases in a
deceleration direction.
Cancels the sleep operation when
feedback value decreases.
Cancels the operation at the rising
edge of the [
WAKE] terminal
Cancels the operation when feedback
value goes below the set value when
[AH-93] is 02.
Is stand-by time for operation cancellation
when [AH-93] is 02.
Cancels the operation when a deviation
between target value and feedback value
increases when [AH-93] is 01.
Description
Starts the sleep function with the terminal
[AH-85] = 02.
Cancels the sleep function with the terminal
when [AH-93] = 03.