Chapter 12
12.17.10
Servo Locking a Motor
Q
• How to fix the position controlling axis.
• How to lock a motor while it stops using vector
control.
A
• This function makes a motor the servo lock status
with the servo lock terminal [SON] command.
• Assigning the input terminal function 054[SON]
triggers this function.
• For the [AA115] stop method selection is 00
SON
FW
Output
frequency
Control
current flows
Parameters
Item
Input terminal function
Stop method selection
Restart after the free-running
is released
Instantaneous power
failure/undervoltage
retry waiting time
*1) Refer to "12.14.3 Starting by picking up
frequency".
!
• If the torque at the time of start is insufficient, it may
be improved by adjusting the starting boost amount
[HC111][HC112] or speed response [HA115].
Refer to "12.9 Select motor control method in
accordance with motor and load".
Not operable because the SON
terminal = OFF
Excitation current does not
flow
Decelerating
stop
Parameter
[CA-01]~[CA-11]
[AA115]
[bb-40]
[bb-26]
0.3~100.0(s)
12-17-33
!
• This is valid when the control method [AA121] is
09: IM 0 Hz range sensorless vector control or 10:
IM vector control with sensor.
• When [SON] is assigned to the input terminal
function, the operation is not accepted unless
[SON] is turned on.
• During the operation, when [SON] is turned off,
there is an operation according to the [AA115] stop
method selection. If the free-running occurs, the
settings for the restart after releasing the
free-running is followed at the time of restart.
• When the backup excitation function [FOC] is
assigned to the input terminal, the servo lock
function [SON] does not operate.
• For the [AA115] stop method selection is 01
SON
FW
Restart after the free-running is released
Output
frequency
Control
current flows
Data
054
Servo lock function [SON]
Perform the deceleration stop when the
00
operation command is off.
Perform the free-running when the operation
01
command is off.
00
Perform the 0 Hz restart.
01
Perform the frequency matching restart. 1)
02
Perform the frequency pull-in restart. 2)
Set the waiting time after an operation
command.
*2) Refer to "12.14.4 Starting with frequency pull-in".
• If the torque at the time of start is insufficient, it may
be improved by using the torque bias function.
Refer to "12.11.6 Operate by Adding Torque
Command".
Inverter Functions
Not operable because the SON
terminal = OFF
Excitation current does not flow
Free-running
Description