Chapter 14
Connection
• When performing a connection, connect each
inverter in parallel as shown below. For the
terminating inverter, short-circuit between terminals
RP
and
SN.
(When
communication
on
between RP and SN likewise.) With the RP-SN
short-circuited, the termination resistor within the
control terminal block board becomes enabled,
which prevents reflection of signals.
External control
equipment
+
SG
!
• As for a cable to connect to TM2, use a shielded
twisted pair cable (0.5mm
mentioned cable is not available, use the following:
• Single cable of 0.14 mm
2
2
(0.14 mm
to 0.5 mm
cables to one pole)
• Stranded cable 0.14 mm
2
2
(0.14 mm
to 0.2 mm
cables to one pole)
you
execute
RS485
one
inverter,
short-circuit
Termination
resistor
Inverter
2
). If the above
2
2
to 1.5 mm
to connect two same size
2
2
to 1.0 mm
to connect two same size
• For communication cables, use shielded cables.
• As for shields, it is recommended that a signal
ground (SG) of external control equipment is
connected to CM1 of an inverter as shown below.
Shield
Inverter
• Stranded cable with rod terminal
2
0.25 mm
to 0.5 mm
(e.g. 1.25=3AF manufactured by J.S.T. Mfg. Co.,
Ltd.)
Cable stripping length 5 mm
Tightening torque 0.22·N・m to 0.25·N・m (screw size
M2)
14-3
RS485 Communication
Termination
resistor
enabled
Inverter
Inverter
2