Chapter 12
12.17 Operating the Inverter in
Conjunction with the System
12.17.1
Using by Switching between Two
Settings
Q
• How to drive two types of motors with different
settings.
• How to retain the settings for two types of motors
separately.
• How to change the settings all together for a batch
production.
A
• This function changes the valid parameters by
assigning 024[SET] to the input terminal function
and turning it on. In conjunction with [SET], the
output terminal 012[SETM] is turned on.
• The following is the notation for the parameters that
are changed with the [SET] terminal.
Example of the Common Settings
Ab - 01
SET Function Type
Parameter Group
Example)
SET Function Type Notation
The third digit of the parameter is "-":
Common
[Ab-01], [bA-30], [CC-01], etc.
The third digit of the parameter is "1":
First setting
[AA101], [bC112], [Hb102], etc.
Second
The third digit of the parameter is "2":
setting
[AA201], [bC212], [Hb202], etc.
Parameters
Item
Parameter
Input terminal
[CA-01]~[CA-11]
function
Output terminal
[CC-01]~[CC-07]
function
In-Group Number
Data
[SET]: Second setting function
OFF: The first setting is valid.
024
ON: The second setting is valid.
*) If the parameter does not have 024[SET] assigned, the
first setting is valid.
012
[SETM]: OFF when SET is OFF; ON when SET is ON.
12-17-1
!
• The [SET] terminal can be switched while the
output of the inverter is blocked. If it is being
switched during the output, it is switched after the
output blockage.
• Even if you want to switch the [SET] terminal for
immediate operation, take more than 1 s for the
switching time.
Example of the First Setting
AA 1 01
SET Function
Parameter Group
Example of the Second Setting
AA 2 01
SET Function Type
Parameter Group
Description
The parameter is common to the first and second settings
regardless of the SET function. Always valid.
If the
[SET] terminal is off or the [SET] function is not
assigned (off), the first setting is applied. The data for
which the third digit of the parameter is "1" are all valid.
If the
[SET] terminal is on, the second setting is applied.
The data for which the third digit of the parameter is "2" are
all valid.
Description
Inverter Functions
In-Group Number
In-Group Number