Chapter 12
1220.3
Outputting a signal when an
operation command exists
• I want to detect the information that an operation
command has been input to the inverter and
convey to the system.
• Assign the output terminal function 031 [FR]
start-up contact signal to one of [CC-01] to [CC-07]
that corresponds to the output terminal and output
the signal.
• The start-up contact signal 031 [FR] is output while
the inverter accepts operation commands.
• The start-up contact signal [FR] is output in
accordance with the state how the operation
command is accepted even when the destination of
the operation command is not a contact.
• The timing chart is as follows.
(Example) In the case of a terminal command
Forward-direction
command [FW]
Reverse-direction
command [RV]
Start-up contact signal
FR]
[
Parameter
Item
Output terminal function
selection 11-15
Relay output terminal
function selection 16A-16C
Relay output terminal
function selection
AL1-AL0/AL2-AL0
Parameter
Data
[CC-01]~[CC-05]
[CC-06]
031
[CC-07]
12-20-3
• When the inverter is operated by using terminal
commands, simultaneous inputs of the
forward-direction command [FW] and the
reverse-direction command [RV] will cause a
command mismatch, which is interpreted as the
stop command. •In this case, the [FR] signal will
not be output.
• The signal becomes ON not only when the motor
is operating at normal rotation but also when a
voltage is output to the motor as a function such as
DC breaking.
• When the operation enable signal 101 [REN] has
been assigned and set to OFF, the signal [FR]
becomes OFF because the inverter cannot be
operated.
Description
[FR]: The start-up contact signal is output
to the output terminal assigned.
Inverter Function