Chapter 12
(2) Bit operation (max. 8-speed command:
[Ab-03]=01)
• Multi-step speeds of 0th to 7th speeds can be
chosen by assigning 007-013 ([SF1]-[SF7]) to the
input terminals 1-9, A, and B [CA-01]-[CA-11].
• The frequency setting of [SF1]-[SF7] should be
made to the multi-step speeds of 1st to 7th speeds
([Ab-11]-[Ab-17]).
Action table
Multi-step
SF7
SF6
speed
0th speed
OFF
OFF
1st speed
-
-
2nd speed
-
-
3rd speed
-
-
4th speed
-
-
5th speed
-
-
6th speed
-
ON
7th speed
ON
OFF
Action chart
0th speed
4th speed
5th speed
3rd speed
6th speed
2nd speed
1st speed
7th speed
SF1
SF2
SF3
SF4
SF5
SF6
SF7
FW
SF5
SF4
SF3
OFF
OFF
OFF
-
-
-
-
-
-
-
-
ON
-
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Frequency command from
the place selected for the
frequency command
1st
spe
12-4-14
• If multiple terminals are made ON simultaneously,
the one with smaller number has priority. "-" in the
table indicates that a frequency is chosen
independently from ON/OFF state of the terminals.
• For the command frequency of the 0th speed, the
command designated in the main speed selection
[AA101] is used. The following table is for
[AA101]=07.
SF2
SF1
Parameters
OFF
OFF
Ab110
-
ON
Ab-11
ON
OFF
Ab-12
OFF
OFF
Ab-13
OFF
OFF
Ab-14
OFF
OFF
Ab-15
OFF
OFF
Ab-16
OFF
OFF
Ab-17
Ex.) 2nd speed is effective.
In this case we have [CA-06]=007 (SF1) and
[CA-07]=008 (SF2).
No assignment is made for 009 (SF3) and 013
(SF7).
Only the input terminal No. 7 (SF2) is ON.
Input terminal
7
6
[SF2]
[SF1]
Multi-
step
SF4
SF3
speed
1st
-
-
speed
2nd
-
-
speed
3rd
-
ON
speed
If SF1 becomes ON in this state, the 1st speed
becomes effective.
Inverter Functions
5
COM
SF2
SF1
-
ON
ON
OFF
OFF
OFF