Chapter 12
12.21.2
Outputting a signal when the
frequency reaches the target
• I want to detect that the output frequency to the
motor has become a frequency larger than the set
value and make a notification to the system.
• Assign the output terminal functions 003 [FA2] and
005 [FA4] exceeding set frequency signal to one of
[CC-01] to [CC-07] that corresponds to the output
terminal and output the signals.
• The signals [FA2] and [FA4] can be output to output
terminal functions individually as the exceeding set
frequency output signal.
• The signals [FA2] and [FA4] will be output when the
enabled output frequency exceeds the setting.
• Operation example
[CE-12]
Output
[CE-10]
Frequency
fon
ON
[FA2]
OFF
ON
[FA4]
OFF
Parameter
Item
Output terminal
function selection
Relay output
terminal function
selection
Relay output
terminal function
selection
Acceleration
reaching frequency
1
Deceleration
reaching frequency
1
Acceleration
reaching frequency
2
Deceleration
reaching frequency
2
fon
Parameter
[CC-01]~[CC-05]
[CC-06]
[CC-07]
[CE-10]
0.00~590.00(Hz)
[CE-11]
0.00~590.00(Hz)
[CE-12]
0.00~590.00(Hz)
[CE-13]
0.00~590.00(Hz)
• The operation of [FA2] can be set through [CE-10]
and [CE-11].
• The operation of [FA4] can be set through [CE-12]
and [CE-13].
[CE-13]
foff
[CE-11]
foff
Data
003 [FA2]: The exceeding set frequency
signal will be output to the output terminal
003
assigned.
005
005 [FA4]: The exceeding set frequency
signal 2 will be output to the output
terminal assigned.
The frequency to judge that the frequency
has been reached in acceleration and
output the signal [FA2].
The frequency to judge that the frequency
has been reached in deceleration and
output the signal [FA2].
The frequency to judge that the frequency
has been reached in acceleration and
output the signal [FA4].
The frequency to judge that the frequency
has been reached in deceleration and
output the signal [FA4].
12-21-2
Inverter Function
fon: 1% of the maximum
frequency
foff: 2% of the maximum
frequency
(Operation example)
Maximum frequency: 60 Hz
When [CE-10] = [CE-11] = 50 Hz
• fon=60×0.01=0.6Hz
• foff=60×0.02=1.2Hz
• In acceleration: On at 50 - 0.6 = 49.4
Hz
• In deceleration: On at 50 - 1.2 = 48.8
Hz
Description