Siemens SIMATIC S5-95F Manual page 266

Table of Contents

Advertisement

Blocks and Their Functions
FB10 (Continued) STL
:
: JU
FB 250
NAME
: RLG: AI
BG
:
KF +8
KNKT
:
KY 1,6
OGR
:
KF +2047
UGR
:
KF - 2047
EINZ
:
F
XA
:
DW 9
FB
:
F
BU
:
F
:
: A
F
: JC
=WEIT
: L
DW 22
: T
DW 9
:
:
WEIT
:
:
:
:
:
:
:
:
: JU FB 251
NAME
: RLG:AQ
XE
:
DW 48
BG
:
KF 1
KNKT
:
KY 0,1
OGR
:
KF +2047
UGR
:
KF - 2047
FEH
:
F
BU
:
F
: BE
9-12
12.0
13.1
13.2
10.0
JU OB 251
13.5
13.6
Explanation
Read setpoint
Slot number
Channel no. 1, fixed-point bipolar
Upper limit for setpoint
Lower limit for setpoint
No selective sampling
Store scaled setpoint in controller DB
Error bit
Range violation
In manual mode, the setpoint is set to the actual
value to force the controller to
react to a system deviation,
if any, with a P step on transfer
to Automatic mode.
*************************
Call controller
*************************
*******************************************************
Output value of manipulated variable Y
*******************************************************
Slot number
Channel 0, fixed-point bipolar
Upper limit for actuating signal
Lower limit for actuating signal
Error bit when limiting value defined
Manipulated variable Y to analog output
Range violation
S5-95F
EWA 4NEB 812 6210-02