S5-95F on SINEC L1
Table 13-5. Initializing the Interface for Failsafe Data Interchange (continued)
Parameters in
Default DB
Slave no. and slave type to which
SNTS1 0 9
data is to be transmitted over
data path 1; default is no data
traffic
Slave no. and slave type to which
SNTS2 0 9
data is to be transmitted over
data path 2; default is no data
traffic
Slave no. and slave type from
SNTE1 0 9
which data is to be received over
data path 1; default is no data
traffic
Slave no. and slave type from
SNTE2 0 9
which data is to be received over
data path 2; default is no data
traffic
Send safety time for data path 1
TD1S 0
Send safety time for data path 2
TD2S 0
Receive safety time for data
TD1E 0 S
path 1 and PLC response
Receive safety time for data
TD2E 0 S
path 2 and PLC response
13-14
Description
Value for
Example
SNTS1 13 5
0 ˆ =No data traffic
1 ... 30 ˆ =Slave No.
31 ˆ = Broadcast
t={1, 5, 9} where
1 ˆ =115F-14 mode
5 ˆ =115F-15 mode
9 ˆ =95F mode
SNTS2 14 9
ˆ = Slave No. (1...30)
n
t ˆ = Mode (1, 5, 9)
SNTE1 13 5
ˆ = Slave No. (1...30)
n
t ˆ = Mode (1, 5, 9)
SNTE2 14 9
ˆ = Slave No. (1...30)
n
t ˆ = Mode (1, 5, 9)
TD1S 17
u=0, 3 to 1638
(times 100 ms)
TD2S 17
TD1E 30 S
p={S, P} where
S=STOP
P=Passivation of the
data paths with
response on user
level
TD2E 30 S
EWA 4NEB 812 6210-02
S5-95F
Permissible
Values
SNTS1 n t
n=1 to 31
SNTS2 n t
SNTE1 n t
SNTS2 n t
TD1S u
TD2S u
TD1E u p
TD2E u p