Module Spectrum
Digital Output Module 8×115 to 230 V AC/0.5 A
1
2
4
.0
3
.1
6
.2
5
.3
8
.4
7
.5
10
.6
9
.7
FF
10A
DIGITAL OUTPUT
8 x 115/230 V AC/0.5 A
6ES5 451-8MD11
1 2
3
4
5
1
3
5
2
4
6
L1
N
X.1 X.0 X.3
X.2
A-14
L1
N
3
6
+9 V
GND
Data
7
9
8
10
X.5 X.4 X.7 X.6
Technical Specifications
Number of outputs
Galvanic isolation
- in groups of
Load voltage L1
- rated value
- frequency
max.
- permissible range
Output current for
"1" signal
- rated value
- permissible range
- lamp load
max.
Contact current
closing rating:
Residual current at
"0" signal
max.
Output voltage
- at "1" signal
max.
Signal Status Display
(green LEDs)
Short-circuit protection
Switching frequency
max.
Permissible current
of all outputs
Driving of digital input
Paralleling of outputs
Length of cable
- unshielded
max.
Rated insulation voltage
(+9 V to L1)
- insulation group
- tested with
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Current consumption
- from +9 V (CPU)
typ.
Power loss of the
module
typ.
Weight
approx.
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2
tested with
Electromagnetic fields
to IEC 801-3
tested with
Fast transient burst
to IEC 801-4
tested with
S5-95F
(6ES5 451-8MD11)
8
yes (optocoupler)
8
115 to 230 V AC
47 to 63 Hz
85 to 264 V
0.5 A
50 mA to 0.5 A
25/50 W
determined by the size
of the fuse
3/5 mA
L1 (-7 V)
only with load
connected
fuse (10 A extra fast)
(Wickmann No. 19231
or 6ESS5 980-3BC41)
10 Hz
4 A
possible
not possible
100 m (330 ft.)
250 V AC
2×B
1500 V AC
12 V AC
1×B
500 V AC
25 mA
3.5 W
270 g (9 oz.)
Severity rating 3
8 kV air discharge
6 kV contact discharge
Severity rating 2
3 V / m
Severity rating 2
1.2 kV on supply lines
1 kV on signal lines
EWA 4NEB 812 6210-02