Technical Specifications
Number of outputs
Galvanic isolation
- in groups of
Load voltage L+
- rated value
- permissible range
(including ripple)
- value at t<0.5 s
Output current for
"1" signal
- rated value
- permissible range
- lamp load
max.
Residual current at
"0" signal
max.
Output voltage
- at "1" signal
max.
Short-circuit protection
Fault LED (red)
Voltage induced on
circuit interruption
(internal) limited to
Switching frequency
- resistive load
max.
- inductive load
max.
Permissible current
of all outputs
Driving of digital input
Paralleling of 2 outputs
- maximum current
Length of cable
- unshielded
max.
Rated insulation voltage
(+ 9 V to L+)
- insulation group
- tested with
Rated insulation voltage
(+ 9 V to
)
- insulation group
- tested with
Current consumption
- from +9 V (CPU)
typ.
- from L+ (without load) typ.
Power loss
of the module
typ.
Weight
approx.
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2
tested with
Electromagnetic fields
to IEC 801-3
tested with
Fast transient burst
to IEC 801-4
tested with
Module Spectrum
(6ES5 451-8MA11)
8
yes (optocoupler)
8
24 V DC
20 to 30 V
35 V
1 A
5 mA to 1A
10 W
0.5 mA
L+ (- 0.6 V)
short-circuit protected
output with autom.
switch
short-circuit
-15 V
100 Hz
2 Hz
6 A
possible
possible in pairs
1.8 A
100 m (330 ft.)
24 V AC
2 x B
500 V AC
12 V AC
1 x B
500 V AC
35 mA
50 mA
3 W
230 g (8 oz.)
Severity rating 3
8 kV air discharge
6 kV contact discharge
Severity rating 2
3 V / m
Severity rating 2
1.5 kV on supply lines
1 kV on signal lines