Siemens SIMATIC S5-95F Manual page 289

Table of Contents

Advertisement

S5-95F
Parameter
Argument
Block ID: SIG
Default setting
SGRP
Z S
Permissible changes
SGRP
z v
Block ID: PERI
Default setting
ST
0 S
ST
31 S
Permissible changes
ST
xRs t
EWA 4NEB 812 6210-02
Define signal groups
When an error is recognized, all signal groups (0 to 31)
respond with PLC STOP
You can assign each signal group its own error response.
Permissible range of values
Signal group z:
z = 0, 1, ..., 31, Z
Response in the case of error v:
v = S, P, L, O, A
S = PLC STOP
P = Passivation
L = Read in previous value
O = ORing of subunit signals
A = ANDing of subunit signals
Slots of the external I/O modules
All slots for external I/O modules are reserved for single-
channel (non-failsafe) modules.
Slot is occupied with failsafe module.
Permissible range of values
Slot no. in subunit A:
x = 0, 2, ... 30
Redundantly operated module belongs to signal group s
s = 0, 1, ... 31
I/O type t
t = DI, DQ
Note:
The slot no. (x + 1) in subunit B must not be parameterized.
Blocks and Their Functions
Explanation
(Z: all signal groups)
9-35