Table 11-4. Analog Input Module 464-8ME11, 4x4 to 20 mA (Absolute Value Representation)
Measured Value
Units
in mA
>4095
> 32.769
4095
31.992
2561
20.008
2560
20.0
2048
16.0
512
4.0
511
3.992
384
3.0
0
0.0
-1
-0.008
<-4095
<- 32.769
*
Because of tolerances of components used in the module, the converted value can also be negative
(e.g. FFF8
Unit: -1).
H
EWA 4NEB 812 6210-02
High Byte
0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 1
0
1
1
1
1
1
1
1
1
0
1
0
1
0
0
0
0
0
0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0
0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 1 1 1 1 1 1 1 1 1 0 0 0
0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
1 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1
Analog Value Processing
Low Byte
1
1
1
1
0
0
0
0
0
0
1
0
0
0
*
Range
Overflow
Overrange
Nominal range
Transducer
failure?
Overflow
11-7