Analog Value Processing
11.5

Analog Output Modules (Type W)

Analog output modules convert the bit patterns that are output by the CPU into analog output
voltages or currents.
11.5.1 Connection of Loads to Analog Output Modules
No adjustments are necessary if you want to connect loads to the analog outputs.
Check the following items before connecting loads:
The load voltage 24 V DC must be connected to terminals 1 and 2.
The maximum permissible potential difference between the outputs is 60 V AC.
Unused outputs must be left open-circuited.
Figure 11-5 shows how to connect loads to the voltage outputs of the module 470-8MA12
(2x ±10 V):
The sensor lines (S+ and S-) must be directly connected to the load, so that the voltage is
measured and regulated directly at the load. In this manner, voltage drops of up to 3 V per line can
be compensated for.
The sensor lines can be left out if the resistances of the QV and M lines are negligible compared to
the load resistance.
In such a case, connect terminal S+to terminal QV, and terminal S- to M
L+
24 V DC
(4/8)
(3/7)
QV
S+
Figure 11-5. Load Connection via a Four-Wire Circuit (6ES5 470-8MA12)
11-8
S+
S-
S+
1
3
5
QV
M
ANA
2
4
6
M
(5/9)
(6/10)
Terminal assignment
S-
M
Terminals
ANA
R
L
S-
7
9
QV
M
ANA
8
10
.
ANA
Key:
QV:
Analog output "Voltage"
S±:
Sensor line
M
:
Chassis ground terminal
ANA
of the analog unit
R
:
Load resistor
L
EWA 4NEB 812 6210-02
S5-95F

Advertisement

Table of Contents
loading

Table of Contents