Siemens SIMATIC S5-95F Manual page 416

Table of Contents

Advertisement

S5-95F
Error Blocks
Beginning in data word DW 64, a detailed report, including the cause of error, auxiliary information
such as the I/O address or count, and the time stamp is entered for each error that occurs. Each
such error report reserves 8 data words, and is sometimes referred to in the following as error
block. The error blocks begin with data word n (n = 64, 72, 80, 88, ..., 184).
To facilitate understanding, the error block is subdivided into bytes which are numbered from 0 to
15.
Data Word
n
Error location
n+1
n+2
n+3
n+4
n+5
n+6
n+7
Evaluation of the error block is discussed in detail in the next section.
EWA 4NEB 812 6210-02
Error Block Contents
System response
Auxiliary info 1
Auxiliary info 2
Auxiliary info 3
Internal data
Internal data
Day (BCD)
Time stamp
Hour (BCD)
Error Diagnosis and Elimination
Main report
Month (BCD)
Minute (BCD)
Bytes
0 and 1
2 and 3
4 and 5
6 and 7
8 and 9
10 and 11
12 and 13
14 and 15
15-9