Expansion of Basic System with External I/Os
When you have a non-floating configuration, you must make certain that the voltage drop on cables
and
does not exceed 1 V. If 1 V is exceeded, the reference potentials could change and the
modules could malfunction.
Warning
!
If you use non-floating I/O modules, you must provide an external connection between
the chassis ground of the non-floating I/O module and the chassis ground of the CPU.
Example of a Floating Configuration with Digital Modules
Floating configuration is required in the following situations.
When you need to increase interference immunity in the load circuits
When load circuits cannot be interconnected
When you have AC load circuits
If you have a floating configuration, the PLC's control circuit and the load circuit must be galvanically
isolated.
Figure 5-23 shows a simplified connection of galvanically isolated I/Os.
1L+
1M
Figure 5-23. Simplified Representation of a Floating, External I/O Connection
5-26
S5-95F
basic unit
L1
N
S5-95F
+9 V
Data
GND
2L+
2M
EWA 4NEB 812 6210-02