S5-95F
Table 15-2. Evaluating System Events in DB254 (continued)
Error No.
(Decimal)
Information
59
Short circuit on sensor circuit
to external DI
(Error response specified in
DB1: Soft STOP or reaction in
user program)
60
SINEC L1 TIMER expired
(Response: Error message)
61
SINEC L1 ok.
(Response: Error message)
62
SINEC L1 framing error
(Response: Error message)
63
SINEC L1 Send length invalid
(Response: Soft STOP)
64
SINEC L1 data path
depassivated
(Response: Error message)
EWA 4NEB 812 6210-02
Primary
Byte 2:
Byte 3:
Byte 5:
Evaluate SINEC L1 error
image mapped into DW 56 of
DB254 (see 15.3.7)
Evaluate SINEC L1 error
image mapped into DW 56 of
DB254 (see 15.3.7)
Evaluate SINEC L1 error
image mapped into DW 56 of
DB254 (see 15.3.7)
Byte 2:
01
H
02
H
Byte 3:
Specified Send length
Byte 2:
0F
F0
Auxiliary
Information
Byte no.
Bit no.
Signal group
:
Data path 1
:
Data path 2
:
Data path 1
H
depassivated
:
Data path 2
H
depassivated
Error Diagnosis and Elimination
Corrective
Measures
Check wiring
Check SINEC L1
master/peer
- Master/peer in RUN
mode
- Check connection/wiring
Check SINEC L1 safety
time
• Increase call interval in
polling list if necessary
Check SINEC L1
master/peer
- Master/peer in RUN
mode
- Check connection/wiring
Check SINEC L1 safety
time
- Increase call interval in
polling list if necessary
Replace SINEC L1 peer's
basic unit if frames frozen
Ignore this message if it
occurs during startup on
the fault-tolerant SINEC L1
LAN.
Select permissible Send
length
Send length must be in
from 1 to 60 bytes
Check wiring
15-17