A Module Spectrum - Siemens SIMATIC S5-95F Manual

Table of Contents

Advertisement

S5-95F
A
Module Spectrum
A.1
General Technical Specifications for Failsafe Modules
Climatic Environmental Conditions
Temperature
Operating
- horizontal design
- vertical design
Storage/transport
Temperature change
- operating
- storage/transport
Relative humidity
Atmospheric pressure
- operating
- storage/transport
Pollutants
- SO
2
- H
S
2
Mechanical Environmental Conditions
Vibration
- tested with
Shock
- tested with
Free-fall
- tested with
Emitted Electromagnetic Interference
Radio interference level
to EN 55011
Electromagnetic Compatibility (EMC)
Noise Immunity
Electrostatic discharge
- Test voltage
EWA 4NEB 812 6210-02
0 to+60 °C (32 to 104 °F)
0 to+40 °C (32 to 104 °F)
(Air-intake temperature,
measured on the underside
of the module)
- 40 to+70 °C
(-40 to 150 °F)
max. 10 °C/h (50 °F/h)
max. 20 °C/h (68 °F/h)
to DIN 40040
15 to 95 % (indoor),
non-condensing
860 to 1060 hPa
660 to 1060 hPa
0.5 ppm,
(rel. humidity 60 %,
non-condensing)
0.1 ppm,
(rel. humidity 60,
non-condensing)
to IEC 68-2-6
10 to 150 Hz,
(const. ampl. 0.15 mm)
57 to 150 Hz,
(const. accel. 2 g)
to VDE 0116
18 shocks
(semisinusoidal 30 g/18 ms)
to IEC 68-2-31
height of fall 50 mm
Limit class A
to IEC 801-2
severity rating 3
8 kV air discharge
6 kV contact discharge
Electromagnetic Compatibility (EMC)
Noise Immunity
Rated electromagnetic
field test
Fast transient burst
Power supply lines
- Supply voltage 24 V DC
Signal lines
- Analog input/output modules
- Digital input/output modules
for V 24 V
Comunications
interfaces
Surge impulse
HF current
IEC/VDE Safety Information
Degree of protection
- Type
- Class
Insulation rating
- between electrically
independent circuits
and
with circuits connected
to a central grounding
point
- between all circuits
and
a central grounding point
(standard mounting rail)
Test voltage
for a rated voltage
V
of the circuits (AC/DC)
input
V
=0 to 50 V
input
V
=50 to 125 V
input
V
=125 to 250 V
input
Module Spectrum
to IEC 801-3,
severity rating 3
field strength 10 V/m
to IEC 801-4,
severity rating 3
2 kV
1 kV
2 kV
1 kV
to IEC 801-5,
severity rating 3
to IEC 801-6,
severity rating 3
to IEC 529
IP 20
I to IEC 536
to VDE 0160
(05. 1988)
to VDE 0160
(05. 1988)
to VDE 0160
(05. 1988)
Sine, 50 Hz
500 V
1250 V
1500 V