A.2 Programmable Controllers - Siemens SIMATIC S5-95F Manual

Table of Contents

Advertisement

Module Spectrum
A.2
Programmable Controller
Technical Specifications S5-95F
Dimensions and Weight
Dimensions WxHxD (in mm)
(in in.)
Weight - S5-95F
Weight - memory submodule approx. 0.1 kg (3.5 oz.)
Internal Technical Specifications
Memory capacity
- internal RAM
- EPROM submodule
Clock
- accuracy t
g
- variation due to temp. change t
Execution time
- per binary operation
Cycle monitoring time
- defined via hardware
- programmable via software
Flags
Timers number/range 128;
Counters number/range 128;
Inputs/outputs (onboard)
Digital inputs, failsafe
Digital outputs
- failsafe
- single-channel
Interrupt inputs, failsafe
Counter inputs, failsafe
External I/O modules
Digital modules
Analog modules
Permissible blocks
Organization blocks
Program blocks
Function blocks
- integrated
Sequence blocks
Data blocks
- reserved
Operation set
Power Supply (Internal)
Input voltage
- rated value
- permissible range
Current consumption from 24 V
- for the subunit
- for full external I/O
configuration
Output voltage
- V 1 (for external I/O)
- V 2 (for programmer)
A-2
145×135×146
5.7 × 5.3 × 5.7
approx. 1.5 kg (3.3 lbs.)
16 KB, 8 KB for
control program
±1 s/day at 25 °C
(77 °F)
0 to 60 °C
A
(32 to 140 °F)
approx. 2 µs
approx. 680 ms
10 to 2550 ms
2048, (512 retentive)
0.01 to 9990 s
0 to 999 (8 retentive)
16
8
2×4
4
2
max.
32
max.
8
1, 2, 3, 13, 21, 22,
31, 34, 37, 251
0 to 255
0 to 255
240 to 243, 250 to
252, and 255
0 to 255
1 to 255
1, 252 to 255
approx. 140
24 V DC
20 to 30 V
typ.
160 mA
typ.
1 A
+9 V
+5.2 V
Output current
- from V 1
- from V 1
Short-circuit protection
Class of protection
Floating
Back-up battery
- life expectancy
- service life (at 25 °C/77° F) approx. 5 years
Power loss of the module
Specific Onboard I/O Specifications
For digital inputs:
Floating
- isolated in groups of
Input voltage
- rated value
- at "0" signal
- at "1" signal
Input current
- at "0" signal
- at "1" signal
Delay time
- from "0" to "1"
- from "1" to "0"
Cable length unshielded
For digital outputs:
Floating
- isolated in groups of
Load voltage L+
- rated value
- permissible range
(including ripple)
Output current for "1" signal
- failsafe outputs
- single-channel outputs
Lamp load
Residual current for "0" signal
Output voltage
- for "0" signal
- for "1" signal
Short-circuit protection
(not overload-resistant)
Limitation of the voltage in-
duced on circuit interruption
- for failsafe outputs
- for single-channel outputs
Switching frequency
- resistive load
- inductive load
S5-95F
(6ES5 095-8FA02)
1 A
0.65 A
electronic
Class I
no
Lithium battery
(3.4 V/850 mAh)
min.
1 year
typ.
12 W
yes
16
24 V
- 30 V to +5 V DC
+13 V to +30 V DC
<1.5 mA (Input
residual current,
2-wire BERO)
<6.5 mA (at 30 V)
typ.
2.5 ms
typ.
2.0 ms
max.
200 m (660 ft.)
yes
16
24 V DC
20 to 30 V DC
max.
0.75 A
max.
0.5 A
max.
10 W
50 µA
max.
0.5 V (at 6 k load
resistance)
max.
L+- 0.5 V (at
0.75 A/0.5A and
24 V DC)
electronic and
thermal
to
- 11 V
to
- 16 V
max.
100 Hz
max.
2 Hz
EWA 4NEB 812 6210-02