Module Spectrum
Analog Output Module 2 x±20 mA (continued)
Technical Specifications
Output range
(rated values)
Number of outputs
Galvanic isolation
Load resistance
Connection method
Digital representation
of output signal
Measured value
representation
Conversion time
(0 to 100 %)
Permissible overload
No-load voltage
Permissible voltage
difference to ground
and between outputs
Basic error limits
(operational error limits
at 25 °C (77 °F), referred
to output range)
Operational error limits
(0 to 60 °C (32 to 140 °F),
referred to output range)
Length of cable
- shielded
Supply voltage L+
- rated value
- ripple V
PP
- permissible range
(ripple included)
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Rated insulation voltage
(Output to L +, between
outputs, output to + 9 V)
- insulation group
- tested with
Current consumption
- from + 9 V (CPU)
- from L +
Power loss
of the module
Weight
A-28
±20 mA
2
yes (outputs to
grounding point and
between outputs)
300
two-wire
connection
11 bits + sign
(1024 units =
rated value)
two's complement
(left-justified)
max.
0.15 ms
25 %
±15 V
max.
75 V DC/60 V AC
±0.3 %
±0.6 %
max.
200 m (660 ft.)
24 V DC
3.6 V
20 to 30 V
12 V AC
1 x B
500 V AC
60 V AC
1 x B
500 V AC
typ.
170 mA
typ.
130 mA
typ.
3.8 W
approx.
290 g (10 oz.)
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2
tested with
Electromagnetic fields
to IEC 801-3
tested with
Fast transient burst
to IEC 801-4
tested with
S5-95F
(6ES5 470-8MB12)
Severity rating 2
8 kV air discharge
4 kV contact
discharge
Severity rating 2
3 V / m
Severity rating 3
2 kV on supply lines
1 kV on signal lines
EWA 4NEB 812 6210-02