Siemens SIMATIC S5-95F Manual page 525

Table of Contents

Advertisement

Module Spectrum
Analog Output Module 2 x 4 ... 20 mA (continued)
Technical Specifications
Output range
(rated value)
Number of outputs
Galvanic isolation
Load resistance
Capacitive load incl.
cable capacitance
Connection method
Digital representation
of output signal
Measured value
representation
Conversion time
(0 to 100 %)
max.
Permissible overload
No-load voltage
Permissible voltage
difference to central
ground point and
between outputs
max.
Basic error limits
(operational error limits
at 25 °C (77 °F), referred
to output range)
Operating error limits
(0 to 60 °C (32 to 140 °F),
referred to output range)
Length of cable
- shielded
max.
Supply voltage L+
- rated value
- ripple V
PP
- permissible range
(ripple included)
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Rated insulation voltage
(outputs to L+,
between outputs,
output to + 9 V)
- insulation group
- tested with
Current consumption
- from + 9 V (CPU)
typ.
- from L+
typ.
Power loss of
the module
typ.
Weight
approx.
A-30
4 to 20 mA
2
yes (outputs to
grounding point and
between outputs)
300
< 100 nF
two-wire connection
11 bits + sign
(1024 units = rated
value)
two's complement
(left-justified)
0.15 ms
25 %
± 15 V
75 V DC/60 V AC
±0.2 %
±0.6 %
200 m (660 ft.)
24 V DC
3.6 V
20 to 30 V
12 V AC
1 x B
500 V AC
60 V AC
1 x B
500 V AC
170 mA
130 mA
3.8 W
290 g (10 oz.)
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2
tested with
Electromagnetic fields
to IEC 801-3
tested with
Fast transient burst
to IEC 801-4
tested with
S5-95F
(6ES5 470-8MC12)
Severity rating 2
8 kV air discharge
4 kV contact discharge
Severity rating 2
3 V / m
Severity rating 3
2 kV on supply lines
1 kV on signal lines
EWA 4NEB 812 6210-02

Advertisement

Table of Contents
loading

Table of Contents